Genetron® 407C (R-407C) Refrigerant | HFC Blend Replacement for R-22 in Commercial & Residential A/C Systems

Category: Brand:

Genetron® 407C (R-407C) is a non-ozone-depleting HFC refrigerant blend developed by Honeywell as a long-term replacement for HCFC-22 (R-22) in commercial, residential, and light industrial air conditioning systems. It is ideal for new equipment and retrofit applications, but is not recommended for flooded evaporator chillers due to its high glide characteristics.

Applications:

  • Residential Air Conditioning

  • Commercial Air Conditioning Systems

  • Commercial Refrigeration

  • Retrofit of R-22-based HVAC systems

Chemical Composition:

  • HFC-32 (Difluoromethane) – 23%

  • HFC-125 (Pentafluoroethane) – 25%

  • HFC-134a (Tetrafluoroethane) – 52%

Technical Specifications:

  • Type: HFC Blend

  • ASHRAE Number: R-407C

  • Molecular Weight: 86.2 lbm/lbmol

  • Boiling Point: –46.5 °F (–43.6 °C)

  • Critical Temperature: 186.9 °F (85 °C)

  • Critical Pressure: 671.5 psia

  • Liquid Density (at 86°F): 69.6 lb/ft³

  • Lubricant Compatibility: Polyol Ester (POE)

Environmental & Safety:

  • Ozone Depletion Potential (ODP): 0

  • Global Warming Potential (GWP): 1774

  • ASHRAE Safety Classification: A1 (Non-toxic, Non-flammable)

  • Flammability Range in Air: None

Genetron® 407C delivers excellent cooling performance and efficiency in systems originally designed for R-22, making it a proven and cost-effective solution for environmentally conscious HVAC transitions.